| Specification | Value |
|---|---|
| Product Name | xPole Residual Current Circuit Breaker (RCCB) |
| Catalog Number | 264306 |
| Model Code | PFGM-63/4/003 |
| EAN | 4015082643065 |
| Product Type | RCCB (Residual Current Circuit Breaker) |
| Application | Residential & commercial circuit protection |
| Number of Poles | 4 poles |
| Tripping Time | Non-delayed |
| Sensitivity (Fault Current) | 30 mA |
| Sensitivity Type | AC sensitive |
| Rated Current | 63 A |
| Rated Operational Voltage (Ue) | 230 V AC / 400 V AC |
| Rated Insulation Voltage (Ui) | 440 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Frequency Rating | 50 Hz |
| Rated Short-Circuit Strength | 10 kA |
| Overvoltage Category | III |
| Pollution Degree | 2 |
| Degree of Protection | IP20 (IP40 with suitable enclosure) |
| Connectable Conductor Section | 1.5 – 35 mm² (solid), 1.5 – 16 mm² (stranded) |
| Terminal Capacity | up to 35 mm² |
| Mounting Method | DIN rail IEC/EN 60715 |
| Dimensions (W×H×D) | approx. 70 × 80 × 76 mm |
| Modular Width | 4 modules |
| Weight | ~0.32 kg |
| Operating Temp. Range | −25 °C to +60 °C |
| Electrical Lifespan | 4 000 operations |
| Mechanical Lifespan | 20 000 operations |
| Standards & Certifications | IEC/EN 61008, RoHS conform |