Surge arrester type 1 4P 12.5 kA 335V avec report
T1-12.5M/335-T4
- Technical support and dedicated single point of contact
- Free delivery from 200€ of purchase (Metropolitan France)
- 100% secure payments
T1-12.5M/335-T4 surge arresters offer complete protection for installations, protecting them from both the direct (when a lightning protector is present) and indirect effects of lightning. They are specially designed to be deployed on single-phase or three-phase networks located in areas characterised by extremely high lightning strike density.
Technical specifications :
- Type 1 and 2 surge protectors
- Rated/maximum current level: Iimp 12.5 kA / Imax 80 kA
- Rated discharge current: In 20 kA
- Integrated thermal disconnection mechanism
Reference : T1-12.5M/335-T4
Mains type : TT-TN
Rated voltage Un : 230 VAC
Max. continuous operating voltage Uc (50Hz) : 335 VAC
Temporary overvoltage withstand : >400 VAC
Rated discharge current In (8/20μs) : 20kA
Maximum discharge current limp (10/350μs): 12.5 kA
Protection level Up under ln: <1.5 kV
Protection level Up under limp: 1.2 kV
Specific energy / load: 40 kJ/Ω 6.25 As
Residual voltage at 5kA / at 10kA / at 15kA / at 20kA: 1 kV / 1.15 kV / 1.25 kV / 1.31 kV
Maximum discharge current lmax (8/20μs): 80kA
Leakage current lpe: < 2mA
Response time: < 25 ns
Max. upstream fuse rating Icc : ≤25kA max.250 A gG/gL
Max. upstream fuse rating Icc : >25kA max.125 A gG/gL
Permissible Icc with max. fuse rating : 25 kA /50Hz
End-of-life indication: yes
Remote reporting of end-of-life information: yes
Connection capacity L; N; PE: 4-35 mmÇ (flexible: 25 mmÇ max.)
Signal terminals: 1.5 mmÇ (flexible, rigid)
Operating temperature: -20°C / +80° C
Housing material: Thermoplastic polyester UL 94 5VA
Degree of protection: IP20
Mounting: Symmetrical DIN rail (EN 50022 / DIN46277-3)
Standards: NF EN 61643-11 / IEC 61643-1